Vapor
13WS, 13WHS
13WS and 13WHS Air
Eliminators improve
the circulation of
pressurized liquids
by eliminating air and
other non-condensible
gases which may
collect at high pointsin the system. The
EPDM valve head
ensures tight shut-off.
Model Í
13WS
13WHS
PMO
150 psig
300 psig
Sizes
3/4” x 3/8”, 1” x 3/8”
3/4” x 3/8”
Connections
NPTConstruction
Cast Iron Body
3
2
Stainless Steel internals w/ EPDM valve head
Options
Brass Body; Stainless Steel Body 13WS only
4
6
Max. Operating Pressure (PMO) 13WS:
150 psig (10barg)
13WHS: 300 psig (21 barg)
5
9
l iMiting o perating C onditions
7
8
10
1
Max. Operating Temperature 13WS & 13WHS: 338˚F (170˚C)
p ressure s hell d esign C onditionsPMA
Max. allowable pressure
TMA
Max. allowable temperature
13WS: 150 psig/0-353˚F
13WHS: 300 psig/0-317˚F
13WS: 450˚F/0-125 psig
13WHS: 450˚F/0-250 psig
10 barg/0-178˚C
21barg/0-158˚C
232˚C/0-9 barg
232˚C/0-17 barg
C onstruCtion M aterials
No.
Part
Material
1
Body
Cast Iron
Brass
Stainless Steel
Cast Iron
Brass
Stainless Steel
Steel
Graphite
StainlessSteel
Stainless Steel
EPDM
Stainless Steel
Stainless Steel
Stainless Steel
Optional 13WS
2
Cover
Pipeline
Pipeline
Auxiliaries
Optional 13WS
3
4
5
6
7
8
9
10
Cover BoltsCover Gasket
Valve Seat
Seat Gasket
Valve Head
Float Arm
Bracket
Float
ASTM A126 CL B
ASTM B62
Type 304
ASTM A126 CL B
ASTM B62
Type 304
ASTM A449
Type 303
Type 304
Type 304
Type301
Type 304
t ypiCal a ppliCations
Air vents can be used on both
hot and cold liquid services.
Typical applications are cold
water lines, suction lines to
pumps, mixing tanks, condensatereturn lines, cooling water
lines on air compressors, and
water storage tanks.
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to...