MINI MCR-SL-UI-UI(-SP)
Configurable 3-Way Isolating Amplifier

Data Sheet

11/2004

Product Description

Features

The configurable 3-way isolating amplifier
MINI MCR-SL-UI-UI(-SP) is used to electrically isolate, condition, amplify, and filter analog signals.
On the input and output side, the standard signals
0...20 mA, 4...20 mA, 0...10 V, 2...10 V, 0...5 V or
1...5 V areavailable, electrically isolated.
The DIP switch accessible on the side of the housing
allows the configuration of the input and output signal
ranges.
The voltage supply (19.2...30 V DC) can either be provided via connecting terminal blocks "3"/"4" or "7"/"8"
of the modules, or together, via the DIN rail bus connector (see Figure 5 on page 6). Please also observe
"Power Supply" on page 7.

Figure1
1
2
3
4
5
6
7
8
9
10

101945_01_en

Features

Input: Standard signals
Transparent cover
Potentiometer for adjustment
Groove for ZBF 6 Zack marker strip
Output: Standard signals
Supply voltage
Connection option for DIN rail bus connector
DIP switch S1
DIP switch S2
Universal snap-on foot for EN mounting rails

1

MINI MCR-SL-UI-UI(-SP)

Technical Data
GeneralData
Supply voltage
Current consumption
Power consumption
Transmission error
With alignment
Without alignment
Temperature coefficient

19.2...30 V DC
< 20 mA
< 450 mW
< 0.1%
< 0.4%

max.
typ.
Cut-off frequency
Step response (10...90 %)
Test voltage (input / output / supply)
Ambient temperature range

< 0.01%/K
< 0.002%/K
100 Hz
3.5 ms
1.5 kV, 50 Hz, 1 min.

OperationStorage
Dimensions (W x H x D)

-20°C…+65°C (-4°F...149°F)
-40°C…+85°C (-40°F...185°F)
6.2 mm x 93.1 mm x 102.5 mm
(0.244 in. x 3.665 in. x 4.035 in.)
0.2...2.5 mm2 (AWG 24...12)

Conductor cross section
Stripping length
Screw connection
Spring-cage connection
Housing design
Tests / Approvals

12 mm
8 mm
Polybutylenterephthalate PBT, green

cu
U PROCESS CONTROL EQUIPMENT FORHAZARDOUS LOCATIONS

LISTED 31ZN
Class I Div 2 Groups A, B, C, D T5
A) This equipment is suitable for use in Class I,
Division 2, Groups A, B, C and D or non-hazardous
locations only.
B) Warning - explosion hazard - substitution of
components may impair suitability for Class 1,
Division 2.
C) Warning - explosion hazard - do not disconnect
equipment unless power has been switched off orthe
area is known to be non-hazardous.

2

101945_01_en

MINI MCR-SL-UI-UI(-SP)

Input (see Figure 1, detail 1)
Input signal range (configurable)

IIN
0...20 mA, 4...20 mA

Max. input signal
Input resistance

50 mA
approx. 50 Ω

Output (see Figure 1, detail 5)
Output signal range (configurable)

IOUT
0...20 mA, 4...20 mA

Load
Ripple
Max. output signal

< 500 Ω
< 20mVss (500 Ω)
28 mA / 12.5 V

UIN
0...10 V, 2...10 V,
0...5 V, 1...5 V
30 V
approx. 100 kΩ
UOUT
0...10 V, 2...10 V,
0...5 V, 1...5 V
≥ 10 k Ω
< 20 mVss
12.5 V / 22 mA

Conformance With EMC Guideline 89/336/EEC And Low Voltage Directive 73/23/EEC
Immunity to Interference According to EN 61000-6-21
Discharge of static electricity (ESD)

EN 61000-4-2

Criterion B2Electromagnetic HF field

EN 61000-4-3

Criterion A3

Fast transients (Burst)

EN 61000-4-4

Criterion B2

Surge voltage capacities (Surge)

EN 61000-4-5

Criterion B2

Conducted disturbance

EN 61000-4-6

Criterion A3

Noise Emission According to EN 50081-2
Noise emission of housing

EN 550114

Class A5

1

EN 61000 corresponds to IEC 1000

2

Criterion B:

Temporaryimpairment to operational behavior that is corrected by the device itself.

3

Criterion A:

Normal operating behavior within the defined limits.

4

EN 55011 corresponds to CISPR11

5

Class A:

101945_01_en

Area of application industry.

3

MINI MCR-SL-UI-UI(-SP)

Ordering Data
Description
Configurable 3-way isolating amplifier
Screw terminal block, preconfigured...