Analisis Sismico De Columnas
PESO LOSA COLUMNAS VIGAS 20% CV TOTAL(KG)
PESO-PISO3 1117007.69 98304 558792 98352.8784 1872456.569
PESO-PISO 2 1645654.412 196608 558792 98352.8784 2655304.29
PESO-PISO 1 1645654.412 196608 558792 98352.8784 2655304.29
PESO TOTAL EDIFICACION 7183065.149
Analisissismico
Fuerza horizontal equivalente
Coeficiente de importancia: 1.25
segun tabla A.4.2.1
coeficiente Ct 0.047
α a: 0.9
h: 9.8
Ta: 0.37
TC= 0.561230769
Tipo de perfil de suelo: F
Para Aa= 0.25 Fa 1.3Coeficiente de importancia I: 1.1
Espectro de Diseño Aproximado (Sa): 1.015625
segun tabla A.4.3.1
Vs= SagM 72953005.42 N
FUERZA SISMICA HORIZONTAL A4.3.1
Fx= CvxVs
Cvx (mxhx^K
∑(mihi^k)
k= 1
PISO mx(kg) hx(m) hx^k mxhx^k Cvx Fx Vx
N N
3187245.6569 9.8 9.8 1835007.4 0.42 30535188.77 30535188.77
2 265530.429 6.4 6.4 1699394.7 0.39 28278544.43 58813733.20
1 265530.429 3.2 3.2 849697.4 0.19 14139272.22 72953005.42
suma 718306.5149 4384099.6 1.00 72953005.42
PROYECTO DISEÑO DE COLUMNAS
AVALUO DE CARGAS
CARGAS PISO 3
CARGAS PESO PROPIO PLACA 240 KG/M2PESO PROPIO DE LOS NERVIOS 214 KG/M2
PESO MUROS INTERIORES 35 KG/M2
CARGA ACABADOS 180 KG/M2
Wcm 669 KG/M2
Wcv 200 KG/M2
PESO COLUMNAS Y VIGAS
b (cm) h (cm) PESO (kg/m) PESO (kg) PESO (KN) PESO COLUMNAS POR PISO (KG)
Col. 1: 80 80 6400 3413333.333 1536 4915.2 49.152 196608
Vig. 1:50 70 3500 1429166.667 840 8467.2 84.672 491097.6
Vig. 2: 30 60 1800 540000 432 432 4.32 67694.4 558792
AREA LOSA
AREA TOTAL 3556224000
VANOS 1097402040
AREA FINAL LOSA 2458821960 mm2 2458.82196 m2
PESO LOSA COLUMNAS VIGAS 20% CV TOTAL(KG) PESO POR CARGA VIVA
PESO-PISO3 1117007.69 98304 558792 98352.87841872456.569 491764.392
PESO-PISO 2 1645654.412 196608 558792 98352.8784 2655304.29 491764.392
PESO-PISO 1 1645654.412 196608 558792 98352.8784 2655304.29 491764.392
PESO TOTAL EDIFICACION 7183065.149 1475293.176 8658358.325
CHEQUEOS Y CALCULOS
EFECTOS P-DELTAPi= 8329822.325 KG
∆cm 36.09 mm
Vi 28831568.31 N
hpi 3400 mm
δcm 97.01 mm
Qi 0.030667293 < 0.1 no considerar efectos p-delta
δpd 3.06915678 mm
CALCULO DERIVA MAXIMA
DERIVA(mm) ∆cad(mm)
δpiso3 77.61 mm 26.92 34 ok
δpiso2 50.69 31.47 32 ok
δpiso1 19.22 19.22 32 ok
∆cmaxCHEQUEO DEL PERIODO
mx(Ton) Fx(Ton)
PISO 3 187.2456569 3053.518877 1.127839031 236.9836
PISO 2 265.530429 2827.854443 0.682274091 143.3439417
PISO 1 265.530429 1413.927222 0.098089171 27.1756812
1.908202293 407.503223
T 0.429958512 seg < Tc
luego no cambia Sa
DISEÑO REFUERZO
Pn >= 873600 N
> As
3.75 cm
4 cm controla
refuerzo transversal
lo
lo 80 cm
53.3 cm
45 cm
por lo tanto
lo= 80 cm
Separacion del refuerzo transversal
Smax...