Bajada De Cargas
ANÁLISIS DE BAJANTE DE CARGAS
1 m² DE LOSA ALIGERADA CON CASETONES DE POLIESTIRENO DE 15 CM DE ESPESOR (AZOTEA)
1 m² DE LOSA ALIGERADA CON CASETONES DE POLIESTIRENO DE 15 CM DEESPESOR (ENTREPISO)
ANÁLISIS DE 1 ml (metro lineal) DE CADENA DE 0.15 x 0.20 m
f¨c= 200 kg/cm² concreto
ARM= 4 vs. 3/8” (No. 3)
Estribos ¼ @ 0.15 mts.
Wconcreto
A=0.15X0.20=0.03m²
V= 0.03 m² (1 m) = 0.03 m³
W= 0.03 m³ x 2400 kg/ m³
W= 72 kg
W reboque
A= 0.20 m x 1m=0.20 m²
V= 0.20 m² x 0.015 m= 0.003m³
W= 0.003m³ x 2100 kg/ m³
W= 6.3 kg (2)= 12.6 kg
Wconcreto= 72 kgWreboque= + 12.6 kg
84.6 kg
TOTAL= 84.6 Kg
ANALISIS DE 1 m² DE PARED DE BLOCK PESADO DE 0.15 X 0.20 X 0.40 m
1 block pesado = 14 kg
W block
12.5 piezas (14 kg)= 175 kg/m²
W reboque
31.5 kg (2) = 63 kg
W mortero
A= 0.15 X 0.20 = 0.03 m²
V= 0.03 m² x 0.015m= 0.00045 m³
W= 0.00045 m³ x 2100 kg/ m³
W= 0.945 kg
A= 0.40 x 0.15= 0.06 m²
V= 0.06 m² x0.015m= 0.0009 m³
W= 0.0009 m³ x 2100 kg/ m³
W= 1.89 kg
W mortero= 0.945 kg + 1.89 kg= 2.83 kg (12.5 piezas) = 35.43 kg
W mortero= 35.43 kg
W block= + 175 kg
Wreboque= 63 kg273.43 kg
W inst.(2%)= 5.46 kg
278.89 kg
+
Viento= 250.00 kg
528.89 kg/m²
ANÁLISISDE 1 ml (metro lineal) DE CASTILLO DE 0.15 x 0.15 m
f¨c= 200 kg/cm² concreto
Wconcreto
A= 0.15X0.15=0.0225 m²
V= 0.0225 m² (1 m) = 0.0225 m³
W= 0.0225 m³ x 2400 kg/ m³
W= 54 kg
W reboque
A= 0.15m x 1m=0.15 m²
V= 0.15 m² x 0.015 m= 0.00225m³
W= 0.00225m³ x 2100 kg/ m³
W= 4.725 kg (2)= 9.45 kg
Wconcreto= 54 kg
Wreboque= + 9.45 kg
63.45 kg
TOTAL= 63.45 KgSUMA DE LOS PESOS PROPIOS DE CADA ELEMENTO:
AZOTEA:
LOSA:
CT= 327.99 kg + 150.0 kg = 477.99 kg/m²
(477.99 kg/m²) ( 24.06m²)= 11,500.43 kg
W MURO DE CARGA: 528.89 kg/m²