Calculos para puestas a tierra en una instalacion subtrerranea
13.2 KV /3 = 7621 KV SOO A = CORRIENTE DE RALLA.
RESISTEN. DE PUESTA A TIERRA = 7621 / 0.5 KA = 15.242 =Ω
TENSION =VOLTAJE FASE A TIERRA = VP / 1.732
RESISTENCIA DE PUESTA A TIERRA.
13.2 KV /3 = 7621 KV 300 A = CORRIENTE DE FALLA
KVA min= 13.2 KV * (0.3 KA / 3) /3= 440 KVA
R (Ω) = 7621 / 0.3 KA = 25.40 Ω
TENSION = VOLTAJE FASE A TIERRA = VP / 1.732
TENSION = 4.4 KV
KVA KVAR
KW
PROTECERONES PARA T- 75 KVA
I N =75KVA3 7621 = S.68 A
I Max = 5.68 × 3 = 17.04 A
I N=25 KVA3 × 7621 = 1.8939 × 3= 5 .6818 A
HACIA ARRIBA
PARA 15°
T=W 2 (sen A + wf cos A)
T=30 × 771 (sen 15°+ 771 × cos 15° )
23103 (0.2588 + 372.36)
T=8, 618, 774,.756
PARA 90°
T= WL (sen A + wf cos A )
T=45 ×771 × 0.5 × cos 90)
T=34 695 (I + 0)
T=34 695
HACIA ABAJO
PARA 45°
T= W2 (senA – wf cos A )
= 771 × 40 (sen 45 –771×0.5 ×cos 45 )
=30840 (192.75 )
=5,944.410
PARA 60°
T= W2 (sen A – wf cos A )
= 771 × 15(sen 60–771×0.5 × cos 60 )
= -2 219 138.166TENSIONES DE JALADO PARA CABLES
Tm = T* n* A
tm= 25* 3* 85.01 = 6375.75 N / mm2
CALCULO PARA JALADO DE CABLES
PARA ANGULO DE LA CURVA EN GRADOS POR TRAMOS RECTOS . PARA JALADO HORIZONTAL.PARA 15° =
TRAMO RECTO T= wf cos A
=771 × 0.5 × cos 15°
T=372 .36
PARA 90° T= wf cos A=771 × 0.5 × cos 90°
T=0
PARA 45° T= wf cos A
=(0.5)× cos 45° × 771
T=545 .179
CALCULO DE CORTOCIRCUITO
I cc permisible =S* 0.0297(logt2+234t1 +234)/.01
T2 = 150° C , TI =75° C , T = 0.1 seg
I cc permissible
=
167, 767.23 *0.0297(log150+234...