Carros Otros
Air System Name Zona2 Banco
Equipment Type Split AHU
Air System Type VAV
Number of zones 1
2. System Components:
Ventilation Air Data: Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method ASHRAE Std 62.1-2007
Unocc. Damper Position Closed
Damper Leak Rate 10 %
Outdoor Air CO2 Level 400 ppmCentral Cooling Data:
Supply Air Temperature 56.0 °F
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule JFMAMJJASOND
Capacity Control ConstantTemperature - Fan On
Supply Fan Data:
Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 1.5 kW
% Airflow|100|90|80|70|60|50|
% kW|100|91|81|72|61|54|
%Airflow|40|30|20|10|0|
% kW|46|40|33|27|21|
Duct System Data:
Supply Duct Data:
Duct Heat Gain 0 %
Duct Leakage 0 %
Return Duct or Plenum Data:
Return Air Via Ducted Return3. Zone Components:
Space Assignments:
Zone 1: Zone 1| |
Caja Fuerte|x1|
Cajas|x1|
Comunicaciones|x1|
Plataforma|x1|
Thermostats and Zone Data:
Zone All
Cooling T-stat: Occ. 74.0 °F
Cooling T-stat: Unocc. 85.0 °F
Heating T-stat: Occ. 70.0 °F
Heating T-stat: Unocc. 60.0 °F
T-stat Throttling Range 1.50 °F
Diversity Factor 1 %
DirectExhaust Airflow 0.0 CFM
Direct Exhaust Fan kW 0.0 kW
Thermostat Schedule N0:Th-Zona2
Unoccupied Cooling is Available
Supply Terminals Data:
Zone All Terminal Type VAV box
Minimum Airflow 3654.0 CFM
Zone Heating Units:
Zone All
Zone Heating Unit Type None
Zone Unit Heat Source Electric Resistance
Zone Heating UnitSchedule JFMAMJJASOND
4. Sizing Data (User-Modified):
System Sizing Data:
Cooling Supply Temperature 56.0 °F
Supply Fan Airflow 3654.0 CFM
Ventilation Airflow ...