HW310
5KV UL Type MV-105, MC-HL, CT Use, 105°C Shielded, EPR Insulation 100% and 133% Insulation Level conductor shield Aluminum Armor copper Copper Conductors conductor
EPRfillers
binder tape
PVC jacket
ground copper welded aluminum tape armor shield
Catalog No. HW310 00603 HW310 00403 HW310 00203 HW310 00103 HW310 10103 HW310 20103 HW310 40103 HW310 25003HW310 35003 HW310 50003
Size AWG/ kcmil 6 4 2 1 1/0 2/0 4/0 250 350 500
No. of ConNo. of ductors Strands 3 3 3 3 3 3 3 3 3 3 7 7 7 19 19 19 19 19 37 37
Insulation Thickness Mils 115 115 115 115115 115 115 115 115 115
Ground Armor DiaWire meter Size Inch AWG 6 6 6 4 4 4 3 3 2 1 1.51 1.64 1.80 1.87 1.94 2.02 2.25 2.41 2.71 3.03
Jacket Overall ThickDiameter ness Inch Mils 50 60 60 60 6060 60 75 75 75 1.61 1.76 1.92 1.99 2.06 2.14 2.37 2.56 2.86 3.21
Net Weight Lbs/Mft 1205 1450 1880 2100 2375 2715 3685 4300 5530 7245
Class I Div. 1 Connector No. 424MA06 424MA06 424MA07424MA07 424MA07 424MA07 424MA08 424MA08 424MA09 424MA10
Rain Tight Connector No. 416MC07 416MC08 416MC08 416MC08 416MC08 416MC08 416MC09 416MC09 416MC09 416MC10
Application: For use in harshenvironments where maximum conductor protection is required. Used for primary power and feeder circuits in a broad range of commercial and industrial power distribution systems. Approved for use in wet or drylocations at 105°C, for installation indoors or outdoors, aerially, in conduits, ducts, cable trays or direct burial in circuits not exceeding 5000 volts. UL listed, Type MC-HL per UL Standard 2225for use in Class I, Division I hazardous locations. UL approved for use at 105°C for continuous operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions. Imperviouscontinuously welded and corrugated aluminum armor cable is recommended as an economical alternative to wire in conduit systems. Conductors: Soft bare annealed copper per ASTM B3, compact Class B...