Diseño De Muro De Contencion
Datos de diseño.
h = 6.00 m f´c = 250 kg/cm2 fy = 4200 kg/cm2
γ = 1.6 T/m3 Q = 15 kg/cm2Factor de carga = 1.6
qn = 16 T/m2 j = 0.87 kg/cm2
θ = 30° fs = 2100 kg/cm2
Calculo de la presión de suelo en elmuro:
Ea(empuje activo) = wh2ka ka = tan2 (45 – θ/2)
2
sustituyendoEa = (1600 kg/m3)(6 m)2[tan2(45 – 30/2)] = 9600 kg/m
2
0.60M = FD = (9600 kg)(2.00m) = 19,200 kgm
Mu Diseño = 1.6(M) = 1.6(19,200 kgm). = 30,720 kgm
4.00 . d=MuQb =3,072,000 kgcm15kgcm2(100 cm)=. =45.25 cm≈60cm
Ea
2.00
Zapata preliminarσ=PA ; A=Pσ , Pvpantalla=6 m0.6 m1 m2400kgm3=8640 kg
A=8640 kg16000 kg/m2=0.54 m2
y
5.25
0.75
x
1.00 0.60 2.10
Pesosvolumétricos
pantalla=0.60 m5.25 m1.00 m2.4tonm3=7.56 ton
zapata=3.70 m0.75 m1.00 m2.4tonm3=6.6 ton
relleno=2.10 m5.25 m1.00 m1.6tonm3=17.64 ton
Elemento | Fy(ton) | Fx(ton) | Brazo(m) | Momento (t.m)|
Pantalla | 7.56 | | 1.30 | 9.828 |
Zapata | 6.66 | | 1.85 | 12.321 |
Relleno | 17.64 | | 2.65 | 46.746 |
Empuje activo | | 9.6 | 2.00 | -19.2 |
Σ | 31.86 | 9.6 | | 49.695 |...