Diseño malla subestacion
SE. SAN SALVADOR TACAZA, LAMPA, PUNO CONSTRUCTORA PEGASO SAC CARLOS RONCAL MADGE
ETAP PowerStation
4.0.0C
Page: Date: SN:
1 04-17-2009 KLGCONSULT
Study Case: MALLA
Filename: p
UNIDAD MINERA TACAZA DISEÑO DE MALLA SE. SAN SALVADOR - TACAZA
Electrical Transient Analyzer Program ETAP PowerStation Ground Grid Systems Finite ElementMethod
Number of Ground Conductors: Number of Ground Rods:
10 8
Total Length of Ground Conductors: Total Length of Ground Rods:
150.00 m 19.00 m
Frequency: Unit System: Project Filename: Output Filename:
60.0 Metric p C:\ETAP 400\PowerStation\TACAZA\p\Malla.GR1
Project: Location: Contract: Engineer:
SE. SAN SALVADOR TACAZA, LAMPA, PUNO CONSTRUCTORA PEGASO SAC CARLOS RONCALMADGE
ETAP PowerStation
4.0.0C
Page: Date: SN:
2 04-17-2009 KLGCONSULT
Study Case: MALLA
Filename: p
UNIDAD MINERA TACAZA DISEÑO DE MALLA SE. SAN SALVADOR - TACAZA
Ground Grid Input Data System Data:
Short-Circuit Current Abmient Freq. Weight Temp. kg °C Hz
60.0 50 40.00
Fault Duration (Seconds) Tf for Total Fault Duration
0.50
Total Fault Current kA
2.000
X/R
1.00Sf Cp Division Projection Factor Factor % %
100.0 100.0
Tc for Sizing Ground Conductors
0.50
Ts for Available Body Cuttent
0.50
Plot Step m
1.0
Extended Boundary Length m
0.0
Soil Data:
Surface Material Material Type
Crushed rock
Upper Layer Soil Depth m
0.1
Lower Layer Soil Depth m
3.0
Resistivity Ω.m
1,000.0
Material Type
Wet organic soil
ResistivityΩ.m
20.0
MaterialType
Bedrock
Resistivity Ω.m
750.0
Material Constants:
Conductivity Conductor/Rod
Conductor Rod
αr Factor @ 20 °C 1/°C
0.00393 0.00378
K0 @ 0 °C
234.0 245.0
Resistivity of Thermal Capacity Fusing Ground Conductor Per Unit Volume Temperature @ 20°C °C
1083.0 1084.0
Type
Copper, annealed soft-drawn Copper-clad steel rod
%
100.0 20.0
μΩ.cm
1.728.62
J/(cm³.°C)
3.42 3.85
Conductor Data:
Size Label
---------------------
Type
Copper, annealed soft-drawn Copper, annealed soft-drawn Copper, annealed soft-drawn Copper, annealed soft-drawn Copper, annealed soft-drawn Copper, annealed soft-drawn Copper, annealed soft-drawn Copper, annealed soft-drawn Copper, annealed soft-drawn Copper, annealed soft-drawn
mm² 120 120 120 120 120 120120 120 120 120
X
0.5 15.5 0.5 0.5 4.2 8.0 11.7 0.5 0.5 0.5
From Y
1.3 1.3 16.3 1.3 1.3 1.3 1.3 5.1 8.8 12.6
Z
0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6
X
15.5 15.5 15.5 0.5 4.2 8.0 11.7 15.5 15.5 15.5
To Y
1.3 16.3 16.3 16.3 16.3 16.3 16.3 5.1 8.8 12.6
Length Z
0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 m 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
Insulated Yes/NoNO NO NO NO NO NO NO NO NO NO
Cost $/m
$20 $20 $20 $20 $20 $20 $20 $20 $20 $20
Rod Data:
Diameter Label
R10 R16
Type
Copper-clad steel rod Copper-clad steel rod
cm 2.00 2.00
X
0.6 15.5
From Y
1.5 1.3
Z
0.5 0.5
X
0.6 15.5
To Y
1.5 1.3
Length Z
2.9 2.9 m 2.4 2.4
Insulated Yes/No
NO NO
Cost $/m
$100 $100
Project: Location: Contract: Engineer:
SE.SAN SALVADOR TACAZA, LAMPA, PUNO CONSTRUCTORA PEGASO SAC CARLOS RONCAL MADGE
ETAP PowerStation
4.0.0C
Page: Date: SN:
3 04-17-2009 KLGCONSULT
Study Case: MALLA
Filename: p
UNIDAD MINERA TACAZA DISEÑO DE MALLA SE. SAN SALVADOR - TACAZA
Rod Data:
Diameter Label
R17 R18 R20 R22 R23 R24
Type
Copper-clad steel rod Copper-clad steel rod Copper-clad steel rod Copper-clad steelrod Copper-clad steel rod Copper-clad steel rod
cm 2.00 2.00 2.00 2.00 2.00 2.00
X
15.5 11.7 0.5 4.2 4.3 11.7
From Y
16.2 12.6 16.3 5.0 12.5 5.1
Z
0.5 0.5 0.5 0.5 0.5 0.5
X
15.5 11.7 0.5 4.2 4.3 11.7
To Y
16.2 12.6 16.3 5.0 12.5 5.1
Length Z
2.9 2.9 2.9 2.9 2.9 2.9 m 2.4 2.4 2.4 2.4 2.4 2.4
Insulated Yes/No
NO NO NO NO NO NO
Cost $/m
$100 $100 $100 $100 $100...
Regístrate para leer el documento completo.