Fuentes conmutadas
SL20.100
Data sheet • • • • • Input: AC 230V Output: 24-28V / 480W (600W) 91% efficiency Ideal for parallel operation Simplefusing
CB scheme
IEC60950 UL508 LISTED IND. CONT. EQ. 18 WM, 60°C
UL60950 E137006 CUL/CSA-C22.2 No 950-M90
EMC and Low Volt. DirectiveInput Input voltage AC 230V, +15%, – 20% 47...63Hz (SL20.300/.301: 3 AC 400/480V, see separate data sheet) AC 184...264V resp. DC 270...370V AC170...280V resp. DC 250...400V 5A typ. 33A at AC 264V
Output Output voltage DC 24-28V adjustable by (covered) front panel potentiometer, preset:24.0V ±0.5% Adjustment range guaranteed Radiated EMI values below EN50081-1, even when using long, unscreened output cables. Operation: 0°C...+70°C(>60°C: Derating) Storage: -25°C...+85°C
Rated Tolerances • Continuous operation • Short term (1 min) at 24 V/20 A Input current Inrush currentOutput noise suppression Ambient temperature range Tamb
Rated continuous loading with convection cooling • Tamb=0°C - 60°C • Tamb=0°C - 45°CDerating Voltage regulation Ripple • Output charact. S • Output charact. P
(S/P: Single/Parallel Mode)
24V/20A (480W) resp. 28V/18A (504W) 24V/25A(600W) resp. 28V/22A (616W) short-term also at 60°C typ. 12W/K (at Tamb= +60°C...+70°C)
Inrush current limiting done with a fixed 15R resistor (nota thermistor) which is bridged after the unit is running, so losses are minimised. That means no reset time even at a warm-start. Fuse loading