DF-52121:C • E-325

MMF-300(A) Series,
MDF-300(A)
Addressable Monitor Modules
Addressable Devices

General
Four different monitor modules are available for Fire•Lite’s
intelligent control panels to suit a variety of applications. Monitor modules are used to supervise a circuit of dry-contact input
devices, such as conventional heat detectors and pull stations,
or monitor and power acircuit of two-wire smoke detectors
(MMF-302(A)).
MMF-300(A) is a standard-sized module (typically mounts to a
4" [10.16 cm] square box) that supervises either a Style D
(Class A) or Style B (Class B) circuit of dry-contact input
devices.

MMF-302(A) is a standard-sized module used to monitor and
supervise compatible two-wire, 24 volt, smoke detectors on a
Style D (Class A) or Style B(Class B) circuit.
MDF-300(A) is a standard-sized dual monitor module used to
monitor and supervise two independent two-wire Style B
(Class B) dry-contact initiating device circuits (IDCs) at two
separate, consecutive addresses in intelligent, two-wire systems.
LiteSpeed™ is a communication protocol developed by
Fire•Lite Engineering that greatly enhances the speed of communication between analogintelligent devices. Intelligent
devices communicate in a grouped fashion. If one of the
devices within the group has new information, the panel CPU
stops the group poll and concentrates on single points. The
net effect is response speed greater than five times that of
other designs. designs.

MMF-300(A) Monitor Module
• Built-in type identification automatically identifies this deviceas a monitor module to the control panel.
• Powered directly by two-wire SLC loop. No additional power
required.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct-dial entry of address: 01 – 159 on MS-9600 series
panels, 01 – 99 on other compatible systems.
• LED flashes during normal operation and latches on steady
to indicate alarm.
TheMMF-300(A) Monitor Module is intended for use in intelligent, two-wire systems, where the individual address of each
module is selected using the built-in rotary switches. It provides either a two-wire or four-wire fault-tolerant Initiating
Device Circuit (IDC) for normally-open-contact fire alarm and
supervisory devices. The module has a panel-controlled LED
indicator. The MMF-300(A) can be usedto replace M300(A)
modules in existing systems.

6999cov.jpg

MMF-301(A) is a miniature monitor module a mere 1.3" (3.302
cm) H x 2.75" (6.985 cm) W x 0.5" (1.270 cm) D used to supervise a Style B (Class B) circuit of dry-contact input devices. Its
compact design allows the MMF-301(A) to be mounted in a
single-gang box behind the device it monitors.

MMF-300(A) (Type H)
may be wired asan NFPA Style B (Class B) or Style D (Class
A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor
(provided) terminates the Style B circuit. No resistor is
required for supervision of the Style D circuit.

MMF-300(A) OPERATION
Each MMF-300(A) uses one of the available module
addresses on an SLC loop. It responds to regular polls from
the control panel and reports its type and thestatus (open/normal/short) of its Initiating Device Circuit (IDC). A flashing LED
indicates that the module is in communication with the control
panel. The LED latches steady on alarm (subject to current
limitations on the loop).

MMF-300(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.0 mA (LED on).
Average operating current: 350 μA (LED flashing), 1communication every 5 seconds, 47k EOL.
Maximum IDC wiring resistance: 40 ohms.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.

MMF-300(A) APPLICATIONS
Use to monitor a zone of...
Leer documento completo

Regístrate para leer el documento completo.

Estos documentos también te pueden resultar útiles

  • Ingenieria en sistemas
  • ¿Que es ingeniería de sistemas?
  • Ingenieria De Sistemas
  • Ingenieria en sistema
  • ingenieria sistemas
  • Ingenieria de sistemas
  • Ingenierio de sistemas
  • Ingenieria en sistemas

Conviértase en miembro formal de Buenas Tareas

INSCRÍBETE - ES GRATIS