Metodo de calculo de agua caliente recirculacion
1. PARA DIMENSIONAR EL DIÀMETRO EL SISTEMA DE SUMINISTRO DEL AGUA CALIENTE REALIZAR EL MISMO PROCEDIMIENTO QUE SE UTILIZA PARA EL SISTEMA DE AGUA FRIA. 2. PARA DIMENSIONAR EL DIÁMETRO DE LA TUBERÍA DE RETORNO PARA CADA RAMAL EN CADA NIVEL TOMAR EL DIÁMETRO DEL ÚLTIMO TRAMO DE LA TUBERÍA DE SUMINISTRO DEL AGUACALIENTE.
3. LAS DOS TUBERÍAS DE RETORNO QUE SE UNEN EN UN MISMO PISO, TOMAR LA DEL DIÁMETRO DE LA MAYOR PARA UNIRLA AL PISO INFERIOR ,
4. SI EL SISTEMA ES PARA UN EDIFICIO DE VARIOS PISOS , REPETIR LOS PROCEDIMIENTOS ANTERIORES PARA UNIR TODOS LOS PISOS HASTA LLEGAR A LA BOMBA DE RECIRCULACIÒN. 5. COLOCAR VÁLVULAS PARA CADA RAMAL (SUMINISTRO Y RETORNO) A LA ENTRADA Y ALA SALIDA DE CADA PISO ONIVEL.
B-
ESCOGER ESPESOR:
EL
MATERIAL DE AISLAMIENTO Y SU
1. DEFINIDO EL DIÁMETRO DE CADA TRAMOS DE LAS TUBERÍAS QUE FORMAN EL SISTEMA DESDE LA SALIDA HASTA LA ENTRADA DEL CALENTADOR. 2. CON LA TEMPERATURA DEL AGUA EN DESCARGA DEL CALENTADOR EN 140°F Y LA TEMPERATURA DE ENTRADA AL CALENTADOR EN 132°F SE ESTABLECE SU TEMPERATURA PROMEDIO. 3. ESTABLECER LA TEMPERATURA AMBIENTE QUERODEA AL SISTEMA
CON LA DIFERENCIA DE LA TEMPERATURA PROMEDIO DEL AGUA CALIENTE Y LA DEL MEDIO AMBIENTE (TOMADO COMO PARÁMETRO) Y CON EL DIÁMETRO DE CADA TRAMO DE LA TUBERÍA DEL SISTEMA SE ESCOJE EL SU ESPESOR DEL AISLAMIENTO SEGÚN LAS GRÁFICAS PRESENTADAS EN LAS SIGUENTES FIGURAS.
LA PÉRDIDA DE CALOR (W / M) DIAGRAMAS DE TUBERÍAS AISLADAS - DESDE 1 / 2 - 6 PULGADAS - ESPESOR DE AISLAMIENTO 0,5A 4 PULGADAS - DIFERENCIA DE TEMPERATURA DE 50 A 350 GRADOS F LOS DIAGRAMAS DE PÉRDIDA DE CALOR A CONTINUACIÓN SE BASA EN TUBOS METÁLICOS CON AISLAMIENTO DE FIBRA DE VIDRIO, CON CONDUCTIVIDAD TÉRMICA 0.25 BTU/H OF FT2/IN, EL ESTADO AL AIRE LIBRE CON VIENTO MODERADO 20 MPH. UN FACTOR DE SEGURIDAD DEL 10% ESTÁ INCLUIDO. W/ft = 3.41 Btu/h ft = 3.28 W/m
Tuberías pérdida de calor - Espesor delaislamiento de 25 mm diferencias de temperatura desde 20 hasta 180 º C
http://www.engineeringtoolbox.com/heat-loss-insulatedpipes-d_1152.html
Heat loss from uninsulated copper pipes ranging 1/2 - 4 inches Heat loss from 1/2" to 4" copper pipes or tubes at various temperature differences between the pipe and the surrounding air, are indicated in the diagram and table below:
Heat loss forthe fluid inside pipe (W/m) Nominal bore Temperature difference (oC)
Heat loss for the fluid inside pipe (Btu/hr ft)
Temperature difference (oF)
(mm)
(inches)
22
38
55
70
100
130
15
1/2
21
32
45
22
34
47
22
3/4
28
43
60
29
45
64
28
1
34
53
76
36
56
79
35
1 1/4
41
64
89
43
6793
42
1 1/2
47
74
104
49
77
108
54
2
59
93
131
62
97
136
67
2 1/2
71
111
156
74
116
162
76
3
83
129
181
87
135
189
108
4
107
165
232
111
172
241
http://www.engineeringtoolbox.com/copper-pipe-heat-lossd_19.html
NOTA 1: NO INSTALAR AISLAMIENTO EN LAS TUBERÍAS O RAMALESDONDE NO RECIRCULA EL AGUA NOTA2: NO DEBE TENER UNA LONGITUD MAYOR DE 6 METROS DESDE QUE SALE DE LA TUBERIA DE SUMINISTRO DE AGUA CALIENTE HASTA EL ARTEFÁCTO. NOTA3: AISLAR TODOS LOS ACCESORIOS Y DETERMINAR LAS PÉRDIDAS DE CALOR EN CADA UNO DE ELLOS.
C-
CALCULO DEL CALOR PERDIDIDO A TRAVES DEL AISLABIENTO q (BTU/HORA)
1. CONOCIDO EL DIÁMETRO DE LA TUBERÍA Y TOMANDO COMO PARÁMETRO LASDIFERENCIAS DE TEMPERATURA SE DETERMINAN LAS PÉRDIDAS DE CALOR EN W/H O EN BTU/H FT.
2. MULTIPLICADO, BTU/HORA PIE LINEAL POR LA LONGITUD DEL TRAMO OBTIENE EL CALOR PERDIDO PARA DICHO TRAMO.
EJEMPLO q ( Td- T1e) ES EL CALOR PERDIDO EN EL TRAMOS DE Td a T1e EN BTU/HORA.
3. SUMAR TODAS LAS PÉRDIDAS DE CALOR DE CADA UNO DE LOS TRAMOS PARA OBTENER EL CALOR TOTAL PERDIDO EN EL SISTEMA QUE ES IGUAL A...