Plantas generadoras
Columbus, Indiana 47201
Basic Engine Model:
Curve Number:
6BT5.9-G5
Engine Critical Parts List:
FR-90491 @ 1500 RPM FR-90490 @ 1800 RPM
Date:
G-DRIVE
ENGINE PERFORMANCE CURVE
Displacement : 5.9 litre (359.0 in ) No. of Cylinders : 6
3
B5.9 1
CPL: 2530
20May99
Bore : 102 mm (4.02 in.) Stroke : 120 mm (4.72 in.) Aspiration :Turbocharged
• • PRELIMINARY • •
Engine Speed RPM 1500 1800 Standby Power kWm 86 101 BHP 115 135 Prime Power kWm 78 91 BHP 104 122 Continuous Power kWm 56 75 BHP 75 100
Emissions Certification:
This engine complies with certain emissions requirements established by US EPA/CARB. See Exhaust Emissions Data Sheet for conformance specifics.
Engine Performance Data @ 1500 RPM
OUTPUT POWER % kWm BHPFUEL CONSUMPTION kg/ kWm·h lb/ BHP·h litre/ hour U.S. Gal/ hour
Litre/hour
1500 RPM (FR-90491)
STANDBY POWER 100 100 75 50 25 100 86 78 59 39 20 56 115 104 78 52 26 75 0.219 0.220 0.225 0.229 0.266 0.226 0.360 0.362 0.370 0.376 0.438 0.370 22 20 16 11 6 15 5.8 5.3 4.1 2.8 1.6 3.9 PRIME POWER
CONTINUOUS POWER
Gross Engine Power Output - kWm
Engine Performance Data @ 1800 RPM
OUTPUTPOWER % kWm BHP FUEL CONSUMPTION kg/ kWm·h lb/ BHP·h litre/ hour U.S. Gal/ hour
U.S. Gallons/hour 1800 RPM (FR-90490)
STANDBY POWER 100 100 75 50 25 100 101 91 68 46 23 75 135 122 92 61 31 100 0.219 0.223 0.233 0.236 0.275 0.232 0.359 0.367 0.383 0.387 0.451 0.380 26 24 19 13 7 20 6.8 6.3 4.9 3.3 1.9 5.4 PRIME POWER
CONTINUOUS POWER
Gross Engine Power Output - BHP
CONVERSIONS:(Litres = U.S. Gal x 3.785) (Engine kWm = BHP x 0.746) (U.S. Gal = Litres x 0.2642) (Engine BHP = Engine kWm x 1.34)
Data shown above represent gross engine performance capabilities obtained and corrected in accordance with ISO-3046 conditions of 100 kPa (29.53 in Hg) barometric pressure [110 m (361 ft) altitude], 25 °C (77 °F) air inlet temperature, and relative humidity of 30% with No. 2 diesel ora fuel corresponding to ASTM D2. See reverse side for application rating guidelines. The fuel consumption data is based on No. 2 diesel fuel weight at 0.85 kg/litre (7.1 lbs/U.S. gal). Power output curves are based on the engine operating with fuel system, water pump and lubricating oil pump; not included are b attery charging alternator, fan, optional equipment and driven components.
TECHNICALDATA DEPT.
CERTIFIED WITHIN 5%
CHIEF ENGINEER
G-DRIVE
B5.9 2
• • PRELIMINARY • • POWER RATING APPLICATION GUIDELINES FOR GENERATOR DRIVE ENGINES
6BT5.9-G5
These guidelines have been formulated to ensure proper application of generator drive engines in A.C. generator set installations. Generator drive engines are not designed for and shall not be used in variable speed D.C.generator set applications.
STANDBY POWER RATING is applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. Under no condition is an engine allowed to operate in parallel with the public utility at the Standby Power rating.
This rating should be applied where reliable utility power is available. A standby ratedengine should be sized for a maximum of an 80% average load factor and 200 hours of operation per year. This includes less than 25 hours per year at the Standby Power rating. Standby ratings should never be applied except in true emergency power outages. Negotiated power outages contracted with a utility company are not considered an emergency.
PRIME POWER RATING is applicable for supplyingelectric power in lieu of commercially purchased power. Prime Power applications must be in the form of one of the following two categories:
UNLIMITED TIME RUNNING PRIME POWER
Prime Power is available for an unlimited number of hours per year in a variable load application. Variable load should not exceed a 70% average of the Prime Power rating during any operating period of 250 hours. The total...