Splicer Marquip
Card and Functional Set-up Procedure
Doc. No: 8990640 Rev. C
07/30/98
Eng: John Baxter Class: Installation Date: 04/08/97 Page 1 of 9
This procedure applies to Marquip Liquid Knives* with the Exit Roll Controller
(ERC) system. The following cards are supported by this procedure.
Pull Exit Control Card--Part Numbers: 9439836, 9454010,or 9454026.
ERC Card----------------Part Numbers: 9454070 or 9454092
NOTE: *Refer to Appendix A if setup is to be applied to an Air Knife.
DECC DRY END CONFIGURATION - KNIFE
1. Select Test and Maintenance from the OIC Main Menu.
2. Select Machine Configuration from the Test and Maintenance Menu.
3. Select Dry End from the Machine Configuration Menu.
4. Move to Dry End Speed Calibrationpage.
5. Leave Knife Calibration unchanged.
6. Set the Knife Offset to 0.00.
7. Set the Knife Overspeed to 1.00.
8. Download the new values.
SPEED CONTROL CARD CONFIGURATION (Pull Roll Portion)
NOTE: For location of test points, switches, LED’s, jumpers and potentiometers
on the Speed Control Card, see Figure 1.
1. Disable the Torque Teaser function and configure Control card per Table 1.Switch Setting Jumper
Speed Control Card S3-2 JP4 JP5 JP6
9439836, 9454010, 9454026 Off On Off On
Table 1.
Note: Spare jumpers are available on SPR1.
2. Set Minimum and Maximum Torque Limits on Control card per Table 2.
Jumper
Speed Control Card JP1 JP2 JP3
9439836, 9454010, 9454026 5 to 6 1 to 2 1 to 2 , 7 to 8
Table 2.
3. Set Default Torque using Switch S2 & S3-1 according to Table 3.Voltage on
TP2 should be within ± 0.1 volts of value specified.
Switch S2 TP2 Switch
Speed Control Card 8 7 6 5 4 3 2 1 (VDC) S3-1
9439836
9454010
9454026
open
open
open
open
closed
open
closed
open
closed
closed
closed
closed
closed
closed
closed
closed
open
closed
open
closed
open
open
open
open
2.16
3.23
2.16
On
Off
Off
Table 3.
4. Verify potentiometer P1 isturned fully clockwise (approximately 25 full
turns). The potentiometer will click when it reaches the rotation limit.
Title: Speed Control Card and ERC (Exit Roll Controller)
Card and Functional Set-up Procedure
Doc.No:
8990640C
Page 2 of 9
EXIT ROLL CONTROL (ERC) CARD CONFIGURATION
NOTE: For locations of test points, switches, LED’s, jumpers and
potentiometers on the ERC Card, seeFigure 2.
1. Configure ERC card for the applicable Knife type per Table 4.
Knife Type JP2 JP3 JP4 U46-1 U46-2 U46-3
98”
72”
110”
Off
Off
Off
Off
Off
On
Off
On
Off
closed
closed
closed
closed
closed
closed
closed
closed
closed
Table 4.
2. Disable Gap and Overspeed for ERC card setup per Tables 5 & 6.
Gap Switch U45
U45-1 U45-2 U45-3 U45-4 U45-5 U45-6 U45-7 U45-8
closed closedclosed closed closed closed closed closed
Table 5.
Overspeed Switch U46
U46-4 U46-5 U46-6 U46-7 U46-8
closed closed closed closed closed
Table 6.
3. In normal operation, the LEDs on the ERC card indicate the following:
LED1...Not Used LED3...Roll Acceleration
LED2...Roll Deceleration LED4...Processor Heartbeat
PULL AND EXIT ROLL SETUP
NOTE: During this procedure all levels have to besetup simultaneously. Try
to match the Pull Roll speeds on all levels since the Knife Configuration
values are not level specific.
1. Remove the end cover or plug from the Pull Roll and Exit Roll motors to
expose the rotor shafts.
NOTE: Roll speeds must be measured with a hand tachometer on the end of the
rotor shaft. Use the following formula to convert from line speed in MPM
(FPM) to rollspeed in RPM.
Roll Speed (RPM) = 2.11063 x Line Speed (MPM)
= 0.64338 x Line Speed (FPM)
2. Run the line at maximum speed or 305 MPM (1000 FPM), whichever is slower.
Adjust the Knife Calibration on the Dry End Speed Calibration page until
the voltage measured at TP1 is as follows. Download the value after each
change.
TP1 = (Line Speed in MPM x 0.02264) volts
or
TP1 = (Line Speed in FPM...