BE3-GPR GENERATOR PROTECTIVE RELAY
Behind-the-Panel Mounting Semi-flush Mounting
Basler Electric’s BE3-GPR generator protective relay offers multiple protective features in a single package. Its microprocessor-based design provides high accuracy, reliability and repeatability. It is extremely easy to set up with an IBM compatible PC or from a menu-driven settings screen or from thefront panel. The digital readout makes calibration quick, easy, and accurate without the need to bench test the relay to verify settings.
FEATURES
• Microprocessor-based design • 10 protective functions • Displays relay set points • Front panel programmability • PC programmable • True RMS sensing • Isolated current inputs • Adjustable trip set points • Adjustable reset set points • Adjustabletime delays for each function • Accepts single phase, three phase 3 or 4 wire voltage inputs • 12 or 24 Vdc power inputs • IEEE C37.90.1-1989 for Surge Withstand • IEEE C37.90.1-1989 for Fast Transient • UL Standard 508 recognized • CSA Standard 14 certified • Gost R Certified #POCC US.ME05-B03391 • Accepts 1 or 5 Amp CT secondaries
DESCRIPTION and FUNCTIONS Pages 2 and 3
FEATURES Page 4SPECIFICATIONS Page 5
WINDOWS® SOFTWARE
Interface for setting and communicating with Basler products (standard) Request BESTCOMS-BE3GPR
INTERCONNECT, DISPLAY and DIMENSIONS Pages 6 and 7 ORDERING INFORMATION Page 8
ADDITIONAL INFORMATION
INSTRUCTION MANUAL
Request Publication 9278200993
ROUTE 143, BOX 269 HIGHLAND, ILLINOIS 62249, U.S.A. PHONE 618-654-2341 FAX 618-654-2351
UEG-87-07
BE3-GPR
DESCRIPTION
BE3-GPR (Generator protective relay) utilizes microprocessor-based technology to provide total generator protection in a single package. This microprocessor design allows for exact set point adjustment and precise generator system protection. BE3-GPR provides multiple functions in a single case, and that adds up to significant installation and setup savings.BE3-GPR allows for direct setup via a PC for easy, fast setup. Low sensing burdens mean that BE3-GPR does not require dedicated PTs and CTs.
PROTECTIVE FUNCTIONS
• 27/59 Under/Overvoltage Trip points are settable from 70 to 600 Vac in 1 volt steps. Reset set points are settable from 70 to 600 Vac in 1 volt steps. Trip timing is adjustable from 0-20 seconds in 1 second steps. Trip points aresettable from 35 to 75 Hz in 0.1 Hz steps. Reset set points are settable from 35 to 75 Hz in 0.1 Hz steps. Trip timing is adjustable from 0-20 seconds in 1 second steps. Trip point is settable from 35 to 75 Hz in 0.1 Hz steps. Reset set points are settable from 35 to 75 Hz in 0.1 Hz steps. Trip timing is adjustable from 0-20 seconds in 1 second steps. Trip point is settable from 50 to 999 Watts in 1 Wattsteps. Reset set points settable from 50 to 999 Watts in 1 Watt steps. Trip timing is adjustable from 0-20 seconds in 1 second steps. Style Option "P" provides single element reverse power protection. Style Option "W" provides three phase three element reverse power protection. Phase Angle is settable from 2 to 20° in 1° steps. Voltage difference is settable from 1 to 100 Vac in 1 volt steps.Time delay is adjustable from .2-2 seconds in 0.1 second steps. Slip frequency is adjustable from .1 to 1.0 Hz in .1 Hz steps. Dead bus is adjustable from 10 to 50 volts in 1 volt steps. Breaker closure is selectable for Gen Hz > Bus Hz only or with Gen Hz > or < Bus Hz. Trip point is settable from 5 to 100 Volts in 1 Volt steps. Reset set points are settable from 5 to 100 Volts in 1 Volt steps. Triptiming is adjustable from 0-20 seconds in 1 second steps. Measures Reactive Current into the paralleled generator. Trip point is settable from 0.15 to 2.5 in 0.01 Amp steps (5 Amp). Trip point is settable from 0.03 to 0.5 in 0.01 Amp steps (1 Amp). Reset point is settable from 0.15 to 2.5 in 0.01 Amp steps (5 Amp). Reset point is settable from 0.03 to 0.5 in 0.01 Amp steps (1 Amp). Trip timing...