Tecnico
APM30 Acceptance Test Procedure for Millicom Project
BOGXXXX LA CASTELLANA
HUAWEI Technologies Co., Ltd. All rights reserved
2011-7-26
Page 1 of 7
HUAWEI APM30 Acceptance Manual RAN12
Table of Contents
OperationGuide........................................................................................................................................ 3 T01 PMU Communication Abnormal ..................................................................................................... 3 T02 Mains Abnormal No AC Power .................................................................................................... 4 T03 Monitor Function TestVoltage,Current,Temperature................................................................... 5
T04 Battery Disconnection Alarm Local Manual Power Off ................................................................ 6 T05 PSU Failure Alarm Module Not In Position .................................................................................. 7
2011-7-26
Page 2 of 7
HUAWEI APM30 Acceptance Manual RAN12
Operation Guide
T01
PMU Communication Abnormal
Objective:When communication line is break, a communication alarm should be reported. Prerequisites BBU is in normal operation. The RUN LED on the front panel of the PMU is twinkling well. There is no alarm in PMU and PSU. Three PSU s are installed in the slot 1, slot 2, and slot 3. All of the Note: The actual number of the PSU is configured by user. Procedure Pull out the RJ45connector on the front panelof the PMU Expected result 1 2 There will be a PMU Internal Interface Communication Failure alarm. After about one minute, the RUN LED on the front panel of the NPMU is twinkling fast. are configured.
Insert the RJ45connector on the front panel of the PMU.
1 2
The PMU Internal Interface Communication Failure alarm is cleared. The RUN LED on the front panel of the PMU is twinkling well.Remarks
Test Result Signature SITE NAME:
PASS
FAIL
NT
Remark Date
2011-7-26
Page 3 of 7
HUAWEI APM30 Acceptance Manual RAN12
T02
Mains Abnormal
No AC Power
Objective: When no AC power input, a mains abnormal alarm should be reported. Prerequisites BBU is in normal operation. The battery is connected to APM30 correctly. The RUN LED on the front panel of theNPMU is twinkling well. There is no alarm in PMU and PSU. Three PSU are installed in the slot 1, slot 2, and slot 3. All of the Note: The actual number of the PSU is configured by user. Procedure Switch off the AC Input Switch of the APM30 in the customer PDB. Expected result 1 The RUN leds on the front panel of the go out. After about twenty seconds, the Alarm led on the front panel of the PMU islighted. There will be Mains Input Out of Range alarm. Fault Cause is No AC Power. are configured.
2
Switch on the AC Input Switch of the APM30 in the customer PDB
1
Wait about twenty seconds, the Alarm led on the front panel of the PMU will be off. All the RUN leds one the front panel of the are lighted.
Remarks Make sure the battery is connected to APM30 correctly. When switch offthe AC power, the battery will supply APM30. Test Result Signature SITE NAME: PASS FAIL NT Remark Date
2011-7-26
Page 4 of 7
HUAWEI APM30 Acceptance Manual RAN12
T03
Monitor Function Test Voltage,Current,Temperature
Objective: User can monitor the Voltage, current and temperature of the APM30. Prerequisites BBU is in normal operation. The RUN led on the front panel of the PMU istwinkling well. There is no alarm in PMU and PSU. Three PSU are installed in the slot 1, slot 2, and slot 3. All of the Procedure Execute following command in LMT: DSP PMU: SRN=7, ITYPE=PMUINFO; NOTE: The voltage, current and temperature information is marked red. Expected result
1 The report is listed as follows:
are configured.
DSP PMU: CN=0, SRN=7, ITYPE=PMUINFO; RETCODE = 0 Succeed....