FUSIBL ES Y B ARRAS SECUNDARIAS PARA
T RANSFORMADORES MONOFÁSICOS 7620240/120 V
.T A B L A DE SEL ECCIÓN DE FUSIB L ES Y B A RRA J ES SECUNDA RIOS
TRANSFORM A DOR
CA L IB RE A WG
CA L IB RE A WG
CA L IB RE A WG
MONOFÁ SICO
L ÍNEA VIVA A L A IRE
NEUTRO
L ÍNEA VIVA EN
NEUTRO
A L A IRE
DUCTO
EN DUCTO
KVA
CA L IB RE A WG FUSIB L E
TIPO K
3
1 x No. 6
1 x No. 8
1 x No. 6
1 x No. 8
0.5
5
1 x No. 6
1 x No. 8
1 x No. 6
1 x No. 8
1.0
10 1 x No. 6
1 x No. 8
1 x No. 6
1 x No. 8
2.0
15
1 x No. 6
1 x No. 8
1 x No. 4
1 x No. 6
3.0
25
1 x No. 2
1 x No. 4
1 x No. 1/0
1 x No. 2
5.0 2 x No. 1/0
37.5
1 x No. 1/0
1 x No. 2
o 1 x No. 4/0
1 x No. 2/0
7.0
1 x No. 1/0
2 x No. 2/0
2 x No. 1/0
10.0
2 x No. 2
50
o 1 x No. 2/0
75 2 x No. 1/0
2 x No. 2
3 x No. 2/0
3 x No. 1/0
15.0
100
2 x No. 2/0
2 x No.1/0
3x No.4/0
3x No.2/0
20.0
USO: Para empalmar los bujes secundarios del trasf ormador monof ásico a la red secundaria de distribución
aérea o subterránea según el caso.
MAT ERIAL : Conductores de cobre para v oltajes de servicio hasta 600 V., aislamiento (color negro) THW o
XLPE.
NOT AS:
· La bajante para barras en ducto de los transf ormadores de 37.5, 50, 75 KVA será en tubería metálica
galvanizada de φ 3” asegurada con cinta metálica al poste.
·
La bajante para barras en ducto de transf ormadores de 100 KVA será en tubería metálica galvanizada
de φ 4” asegurada con cinta metálica al poste.
·Las bajantes, barrajes y red secundaria donde la línea está conf ormada por varios conductores por
f ase, se deberán empalmar entre sí en cada punto de derivación.
·...