Alarm Fanuc Ot
011
The specified feedrate is zero
Check the feedrate parameter specified with a function code
013
The specified feedrate (maximum feedrate) is Check the value of parameter No. 043, which indicates the zeromaximum feedrate that can be specified. More than 32 blocks have been registered for Reduce the number of registered blocks to 32. a buffering operation. Input from the reader/puncher interface or the Correct the baud of the input/output unit (always 4800) or like caused an overrun, parity, or framing other settings. error) Input from the reader/puncher interface or the like includes an input/outputunit operation Turn the reader/puncher on. Check the cable connection. ready signal (DR) that is set to off. After input from reader/puncher interface or the like stops, character input does not stop Check the cable connection. even though ten characters have been input. Move the tool in the direction of reference position return in Reference position setting cannot be executed jog mode at a speedthat causes the servo position error to normally. exceed 128. Then, specify another reference position A first to third reference position return cannot be executed because the reference position Set the reference position. has not yet been established. The reference position has not yet been established. This occurs only when the ZRTN Set the reference position. bit of parameter No.001 is set to0. Input data 1 is invalid. Check input data 1, specified with a function code.
070
085
086
087
090
093
224
250
251
Input data 2 is invalid. Operation can not be activated because an invalid mode is specified or because block execution is in progress. The interface switch signal (DRC) was switched during block execution.
Check input data 2, specified with afunction code.
255
Check the mode. Check whether a block is being executed.
290
Switch the signal after block execution stops.
291
The speed of an axial movement specified by Check the speed specified by the external pulse. Check an external pulse has exceeded the upper the magnification of the external pulse (parameters No.062 limit. This occurs only when the EPEXA bit of and 063).parameter No.001 is set to 1. A checksum error for the battery-powered memory was detected Parameters are cleared. Set the parameters again. If this alarm subsequently recurs, replace the unit.
292
Pulse coder alarms No. LED display Description Countermeasure Check the continuity of the signal cable. If the cable is normal, the pulse coder may be defective. Turn the power off. If the alarmrecurs, replace the serial pulse coder and motor.
300
A communication error (DTER) for the serial pulse coder was detected.
301
A communication error(CRCER) for serial pulse coder was detected.
Check the continuity of the signal cable. If the pulse coder is normal, the pulse coder or servo unit may be defective. This error can also be caused by external noise.
302
Acommunication error (STBER) for serial pulse coder was detected.
Check the continuity of the signal cable. If the cable is normal, the pulse coder or servo unit may be defective. This error can also be caused by external noise.
303
An LED disconnection (LDAL) was detected in Turn the power off. If this alarm recurs when the power is the serial pulse coder. reapplied, replace the motor. A mispulsealarm (PMAL) for the serial pulse Turn the power off. If this alarm recurs when the power is coder was detected. reapplied, replace the motor. A miscount alarm (CMAL) for the serial pulse Turn the power off. If this alarm recurs when the power is coder was detected reapplied, replace the motor.
304
305
306
The motor was overheated (OHAL).
This alarm is issued when the amplifier has...