Cambio De Voltaje Y Frecuencia En Un Equipo Cummins
Open the panel of the Power Command.
To get down the speed of the engine (RPM) andfrequency, turn the precision screw of the engine governor inside the panel counterclockwise (about two and a half turns).
1
Go to the control panel andpress any button to start the communication between the engine and the Power Command. Press both arrows for a few seconds at the same time.
SelectOption one (1, Setup Menu)
2
The system will ask for a password, wish is 574, (you can navigate around the digits and change them with the buttons +,- and the arrow), to go to the next screen, press the arrow.
Select the option one (1, Gen-set Service).
3
Select the option one (1,Gen-set).
Select the button “ADJUST”.
4
Now you can change the voltage and frequency configuration navigating with the buttons +, - and the arrow.
Press the button “SAVE”.
5
Press, in the Power Command Control the button Previous Menu several times, until the main screen shows up.
Turn on the generating group (The frequency will not be the desire one yet). Pres any of the arrows until you get to the screen who shows up thefrequency and speed, (RPM).
Now, whits the engine on and very carefully, continues turning the precision screw of the engine governor until you getthe desire frequency and speed. For a 50 Hz frequency, you will need about 1500 RPM. For a 60 Hz frequency, you will need about 1800 RPM.
6
Regístrate para leer el documento completo.