F0-4AD2DA-1 4-CH. IN/2-CH. OUT ANALOG CURRENT COMBINATION
In This Chapter...

CHAPTER

11

Module Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11–2 Setting the Module Jumper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11–4 Connecting and Disconnecting the Field Wiring . . . . . . . . . . .. . . . . . . . . . . . . . .11–5 Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11–6 Module Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11–7 Special V-memory Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11–8 Usingthe Pointer in Your Control Program . . . . . . . . . . . . . . . . . . . . . . . . . . . .11–11 Scale Conversions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11–13 Module Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11–16 Analog Input Ladder Logic Filter . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .11–17

Chapter 11: F0-4AD2DA-1 4-Ch. In/2-Ch. Out Analog Current Combination

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Module Specifications
The F0-4AD2DA-1 Analog Combination module offers the following features:
• The analog input and output channels are updated in one scan. • The removable terminal block makes it possible to remove the modulewithout disconnecting the field wiring. • Analog inputs can be used as process variables for the four (4) PID loops in the DL05 and the eight (8) PID loops in the DL06 CPUs. • On-board active analog filtering and RISC-like microcontroller provide digital signal processing to maintain precise analog measurements in noisy environments.

R PW

N RU
U CP

TX1 1 RX TX2
2 RX

NOTE: The DL05CPU’s analog feature for this module requires DirectSOFT32 Version 3.0c (or later) and firmware version 3.30 (or later). The DL06 requires DirectSOFT32 version V4.0, build 16 (or later) and firmware version 1.00 (or later). See our website for more information: www.automationdirect.com.

11–2

DL05/06 Option Modules User Manual; 7th Ed. Rev. A, 08/11

Chapter 11: F0-4AD2DA-1 4-Ch. In/2-Ch.Out Analog Current Combination
The following tables provide the specifications for the F0–4AD2DA–1 Analog Combination Module. Review these specifications to make sure the module meets your application requirements. Input Specifications
Number of Channels Input Range Resolution Step Response Crosstalk Active Low-pass Filtering Input Impedance Absolute Maximum Ratings Converter type Linearity Error(End to End) Input Stability Full Scale Calibration Error (Offset error not included) Offset Calibration Error 4, single ended (one common) 0 to 20 mA or 4 to 20 mA (jumper selectable) 12 bit (1 in 4096) for 0-20mA, scaled for 4-20mA 25.0 ms (typ) to 95% of full step change -80 dB, 1/2 count maximum * -3 dB at 40Hz (-12 dB per octave) 125 Ohm _0.1%, 1/8 W current input -30 mA to +30 mA currentinput Successive approximation ±2 counts ± 1 count * ± 10 counts maximum @ 20mA current input*

± 5 counts maximum @ 0mA current input * ±.4% @ 25°C (77°F) Maximum Inaccuracy ±.85% 0 to 60°C (32 to 140°F) ±100 ppm typical full scale calibration Accuracy vs. Temperature (including maximum offset change) Recommended Fuse (external) 0.032 A Series 217 fast-acting, current inputs *One count in thespecification table is equal to one least significant bit of the analog data value (1 in 4096).

Output Specifications
Number of Channels Output Range Output Type Resolution Maximum Loop Voltage Load (ohms)/Loop Power Supply Linearity Error (end to end) Conversion Settling Time Full Scale Calibration Error Note: Error depends on the load from source terminal to ground. 2, single ended (one...
Leer documento completo

Regístrate para leer el documento completo.

Estos documentos también te pueden resultar útiles

  • analoga 1
  • Analogica 1
  • ANALOGICOS 1
  • Analogica 1
  • CASO TARGET 1
  • Informe de Analoga 1 nuevo
  • Analog A Inusual 2 1
  • Lab 1 Analogas

Conviértase en miembro formal de Buenas Tareas

INSCRÍBETE - ES GRATIS