Instruction Bulletin
SDSA1175 Series 001
Secondary Surge Arrester

Bulletin No. 8291-0014D October 2001 Raleigh, NC USA

INTRODUCTION

The SDSA1175 Secondary Surge Arrester is designed and listed for indoor or outdoor installation and surge protection of single-phase threewire 120/240 Vac 60 Hz electrical services and major appliances. Two SDSA1175 Secondary Surge Arresters can beinstalled to provide protection on 208Y/120 Vac three-phase four-wire services. NOTE: Use on solidly grounded systems only.

PRECAUTIONS

DANGER
HAZARD OF ELECTRIC SHOCK, BURN OR EXPLOSION. • This equipment must be installed and serviced only by qualified electrical personnel in accordance with National and Local Electrical Codes. • Turn off all power supplying this equipment before working on orinside equipment. • Always use a properly rated voltage sensing device to confirm power is off. • Replace all devices, doors, and covers before turning on power to this equipment. • Do not apply petroleum-based products to non-metallic parts. Failure to follow these instructions will result in death or serious injury.

CAUTION
HAZARD OF EQUIPMENT DAMAGE. Megger ® or hi-potential tests will damagethis surge protective device. Turn off all power supplying the equipment and isolate the surge protective device before testing. Failure to follow these precautions can result in equipment damage.

© 2001 Schneider Electric All Rights Reserved

1

SDSA1175 Series 001 Secondary Surge Arrester Instruction Bulletin

Bulletin No. 8291-0014D October 2001

INSTALLATION

1.

Turn off allpower supplying this equipment before working on or inside equipment. 2. See Figure 1. 3. Confirm SDSA is rated for your system by comparing voltage measurements to the Line Voltage (L-L, L-N) on the product label. 4. Install in accordance with article 280 of the National Electric Code. 5. Confirm that the electrical terminals used to attach this device are identified for these conductors. 6.Twist conductors 1/2 turn or more for every 12 inches of length. 7. Keep conductor length as short as possible with no sharp bends. 8. Do not loop or coil wires. 9. Ensure a high quality ground is in place. 10. Install cover and/or close door on equipment.
Black

Nut 0.5 in. [13 mm] knockout (trade size) Actual hole size .875 in. [22 mm]

Black White Black

White Black Black

White

NOTE:The secondary surge arrester must be installed in an accessible location (not within walls). When installing secondary surge arrester inside a QO or HOM load center, do not remove an enclosure knockout. Use optional QOSAMK surge arrester mounting kit. Refer to instructions included with the QOSAMK kit.

Black

Figure 1: Mounting SDSA Unit
Single-phase Three-wire 120/240 Vac Two Surge Arresterson 208Y/120 Vac Three-phase Four-wire Service

Figure 2: Wiring Diagrams

Diagnostic Operation • LED ON = Normal operation • LED OFF = Fault, check phase voltage, breakers (if used) and connections. If OK, replace unit. (see Figure 3)
ON = OK OFF = Fault

Figure 3: Diagnostic Operation

General Specifications
Product Catalog No. Max Surge Current Housing Rating Product Weight ConnectionMethod Thermal Fusing Operating Temperature Operating Frequency Diagnostics Product Standards SDSA1175 36 kA/Phase Type 4X .525 lb Parallel, #14 AWG Stranded Wire Yes -40˚ to +160˚F (-40˚ to +70˚C) 50/60 Hz Green Status LED UL 1449-2nd Ed, cUL, ANSI/IEEE C62.11 Surge Arrester/TVSS

2.685 [68] 2.250 [57] 1.935 [49]

2.250 [57]

Dimensions: in. [mm]

Figure 4: Dimensions

Square D 8001Hwy 64 East Knightdale, NC 27545 USA 1-888-SquareD (1-888-778-2733) www.SquareD.com

Electrical equipment should be serviced only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. This document is not intended as an instruction manual for untrained persons. © 2001 Schneider Electric All Rights Reserved