6. Mediciones realizadas liberado el segmento de bus de campo.
Measure resistance from the:
+ Signalconductor to - Signal conductor + Signal conductor to drain/shield wire - Signal conductor to drain/shield wire + Signal conductor to instrument ground bar - Signal conductor to instrument ground bar drainshield/wire to instrument ground bar
Expected result > 50 KΩ (increasing)
open circuit > 20 MΩ open circuit > 20 MΩ open circuit > 20 MΩ open circuit > 20 MΩ open circuit > 20 MΩ
Troncal H1Troncal c/ Spurs >3.369MΩ 0L 0L 0L 0L 0L >3.369MΩ 0L 0L 0L 0L 0L
Measure capacitance from the:
Expected result
1 microF(0.80 to1.20 uF acceptable)
+ Signal conductor to - Signal conductor +Signal conductor to drain/shield wire - Signal conductor to drain/shield wire + Signal conductor to instrument ground bar - Signal conductor to instrument ground bar drain shield/wire to instrumentground bar
1.6 uF 6nF 6nF 1nF 1nF 2nF
1.6 uF 9nF 9nF 3nF 4nF 5nF
< 300 nF < 300 nF < 300 nF < 300 nF < 300 nF
Observaciones Las mediciones están dentro de los parámetros permitidos. Laconexión o adición de Spurs varían los valores de capacitancia en forma ascendente. Los valores de capacitancia (terminaciones +/-) varían (incrementan) cuando se desconecta el terminador y/o cuando seaterra el cable shield, y la resistencia se mantiene > 1,7 MΩ La caída de tensión varía relativamente en 1 o 2 %.
7. Mediciones realizadas con Spurs
Medición _Terminales +/Sin Spurs Con SpursResistance Capacitance Resistance Capacitance + Signal conductor to drain/shield wire 2.6 MΩ 1.6 uF 3.0 MΩ 1.6 uF conexión - Signal conductor to drain/shield wire 1.6 uF 3.0 MΩ 1.6 uF corto ckt 2.7MΩ drain shield/wire to instrument ground bar 3.4 MΩ 1.6 uF 3.0 MΩ 1.6 uF Sin terminador drain shield/wire to instrument ground bar 2.4 MΩ Terminales
28 nF
1.7 MΩ
Mediciones en la Troncal...