Configurar un enlace entre el wincc flexible runtime (pc/panel) y un s7-300/400 a través de profibus/mpi
What should you watch out for when setting up a connection between S7200 and SIMATIC Panels or WinCC flexible PC Runtime and what are the options?
WinCC flexible, SIMATIC Panels and SIMATIC S7-200 FAQ November 2009
Service & Support
Answers for industry.
Question
This entry originates from the Service&Support Portal of Siemens AG, Sector Industry, Industry Automationand Drive Technologies. The conditions of use specified there apply (www.siemens.com/nutzungsbedingungen). Go to the following link to download this document. http://support.automation.siemens.com/WW/view/de/28263099
Question
What should you watch out for when setting up a connection between S7-200 and SIMATIC Panels or WinCC flexible PC Runtime and what are the options?
Answer
Follow theinstructions and notes listed in this document for a detailed answer to the above question.
2
FAQ-Kurztitel Version , Entry ID: ID-Nummer
Contents
Contents
1 1.1 1.1.1 1.2 2 2.1 2.1.1 2.1.2 2.2 2.3 2.3.1 2.3.2 3 3.1 4 4.1 4.2 4.3 4.4 Connection via PROFIBUS .................................................................. 4 Configuration in WinCC flexible........................................................... 4 Settings in the configuration................................................................. 4 Settings in STEP 7 Micro/WIN ............................................................. 6 Connection via Ethernet (CP243-1) ..................................................... 7 Requirements....................................................................................... 7 Connection between S7-200 and WinCC flexible PC Runtime ........... 7 Connection between S7-200 and Windows-based operator panels.... 7 Configuration of the CP 243-1 with STEP 7 Micro/WIN....................... 8 Configuration ...................................................................................... 13 WinCC flexible PC Runtime............................................................... 13 Windows-based operator panel ......................................................... 16 Connection via RS232/PPI cable ....................................................... 19 Connection between WinCC flexible PC Runtime and an S7-200 controller............................................................................................. 19 Connection via TeleService............................................................... 23 Requirements ..................................................................................... 23 Direct connection between a TS Adapter II-Modem and an S7-200 controller............................................................................................. 23 Direct connection between a TS Adapter II-Modem and an S7-200controller and a panel via MPI............................................................ 24 Direct connection between a TS Adapter II-Modem and an S7-200 controller, an S7-300 controller and a panel via MPI ......................... 25
S7-200 Connection with WinCC flexible and SIMATIC Panels Version , Entry ID:28263099
3
1 0BConnection via PROFIBUS
1
1.1
Connection via PROFIBUSConfiguration in WinCC flexible
If you want to connect a WinCC flexible operator panel to an S7-200, please make sure that the S7-200 is only operated as a DP slave. The panel or PC must be used on the PROFIBUS DP network as DP master and the S7-200 as DP slave.
1.1.1
Settings in the configuration
You must make the following settings in the WinCC flexible configuration.
Table 1-1 No. 1. Procedure In WinCC flexible, you configure a controller connection to the S7-200 under "Project > Communication > Connections".
2.
To set up a communication between the S7-200 as DP slave and the PC as DP master, you check the option "Only master on the bus".
Example:
4
S7-200 Connection with WinCC flexible and SIMATIC Panels Version , Entry ID: 28263099
1 0BConnection...