Inst. electricas
COMPARACION ENTRE LOS METODOS OHMICO, P.U. y MVAS 13.8 KV , 3 FASES, 60 Hz, Pot.c.c.= 500MVA
Alimentador X = 0.151 Ohms
Transformador 5000 KVA Rel 13.8/2.4 KV , X = 0.055 p.u. F 2.4 KV
Motor 2500 KVA X”d = 0.16 p.u. DIAGRAMA UNIFILAR
CALCULOS DE LA CORRIENTE DE CORTO CIRCUITOTRIFASICA Prof: Ing. Ricardo A. Espinosa y Patiño Hoja 2 de 6
METODO OHMICO 2.4 KV BASE 1 SISTEMA
X1 1000X ( KV ) KVAs
2
METODO POR UNIDAD METODO DE LOS 500 000 KVA BASE MVAs KVA X (1)MVA1= 500 X1 KVA
Base c .c .
1000X (13.8) 2 500000
X2
500000 (1) X 500000
2 ALIMENTADOR
= 0.38 (*) X 2 0.151 (*)
=1.0 p.u.
( Ohms) X ( KVABase ) 1000X ( KV 2 )
MVA2 ( KV 2 ) X Ohms
0.151X 500000 1000X 13.8 2
.8 13151 0.
2
0.396 p.u.
=1260
MVA3
MVAT X p .u .
3 TRANSFORMADOR
X
3
1000X ( Xp .u ) X ( KV ) 2 KVAT
2
X3 ( X p . u . ) X ( KVABase ) KVAT
= 1000X 0.055X 2.4 5000 = 0.063 4 MOTOR
0.16 = 1000X 2500X 2.4 = 0.369
2
0.055X 500000 5000
= 91
MVA4
MVAM X p .u .
5.5 p.u.
X 4 1000X ( Xp .u.) X ( KV ) KVAM
2
X4
( X p . u . ) X ( KVABase ) KVAM
X 500000 0.162500 32.0 p.u.
2.5 0.16
=15.6
(*) Se requiere referir a la Tensión Base la cual esgeneralmente la tensión en donde se ubica la falla a calcular.
CALCULOS DE LA CORRIENTE DE CORTO CIRCUITO TRIFASICA Prof: Ing. Ricardo A. Espinosa y Patiño Hoja 3 de 6
METODO OHMICO:
1
SistemaX1 = 0.380 Ohms referida a 13.8 KV
2
Alimentador
X2 = 0.151 Ohms referida a 13.8 KV X1+X2 = 0.531 Ohms referidas a 13.8 KV X1+X2 = 0.531 x 0.03(**) = 0.016 Ohms referidas a 2.4 KV (**) X3 =0.063 Ohms referida a 2.4 KV X1+X2+X3 = 0.079 referida a 2.4 KV = X1,2,3 SERIE X4 = 0.369 Ohms referida a 2.4 KV X1,2,3 + X4 = 0.0656 Ohms referida a 2.4 KV PARALELO = X eq MVAcc = KV2/Xeq =...