Tyco,biffi,epi
EPI2-MAN-652NA-OM1
I/O Module
User’s Manual
2 NA 2 NA 2 NA 2 1 0 Rev.
June 07 May 07 Sept. 06 Jun 06 Feb 06 Sept 2005 Date
N.A Version revision 2 of N.A Version revision 1 N.A Version Created Revision Revision First Issue DESCRIPTION
T.K. T.K. / D. L. P. T.K. / D. L. P. A.G. A.G. A.G. Prepared G.A. G.A. G.A.Approved
Note: Tyco Valves & Controls has taken every care in collecting and verifying the documentation contained in this Instruction and Operating Manual. The information herein contained is reserved property of Tyco Valves & Controls.
® Copyright by Tyco Valves and Controls. All rights reserved. A tyco International Ltd. Company
1
EPI2 Quarter-turn Electric Actuators Instructionand operating manual
INDEX
OPTIONAL MODULE 1 (OM1)............................................................................................................... 3 INSTALLATION........................................................................................................................................ 3 SETTING AND CONFIGURATION....................................................................................................... 6 MONITOR RELAY FUNCTIONALITY AND SETTING .................................................................. 10 1. OM1 WIRING DIAGRAM.............................................................................................................. 11
2
® Copyright by Tyco Valves and Controls. All rights reserved. A tyco International Ltd. CompanyEPI2 Quarter-turn Electric Actuators Instruction and operating manual
OPTIONAL MODULE 1 (OM1)
The optional OM1 I/O module can be installed by the factory or ordered as a kit and installed in the field. The OM1 provides the following functions: • Positioner that will accept an analogue signal input of 4-20 mA or 0-10 Vdc or can be turned off to allow use of module as aretransmission/monitor relay/additional switch module only • Position transmitter with an output of 4-20 mA or 0-10 Vdc • Monitor relay that provides a remote indication for loss of power, over-torque alarm, motor over- temperature alarm and travel alarm and selector switch position • Motor running • 4 additional SPST output contacts that can be set independently at 10 locations along the stroke. Contacts areconfigurable (make or break).
INSTALLATION
To install the OM1 into the actuator, proceed as follows: The OM1 option kit consists of the following parts: - OM1 modulating input/output module - 3 metal spacers (models 006 and 013 only) - 4 screws - 1 flat cable with connectors
Fig.1: OM1 kit
With an Allen wrench remove the cover screws. The screws are not captive. (Fig. 2):
Remove the actuatorcover (Fig.3):
Fig. 2
Fig. 3
® Copyright by Tyco Valves and Controls. All rights reserved. A tyco International Ltd. Company
3
EPI2 Quarter-turn Electric Actuators Instruction and operating manual
Pull out the 4 black cables (already installed in the base actuator) (fig. 4)
Remove the local mechanical indicator by pulling upward (fig. 5)
Fig. 4
Fig. 5
Connect theflat ribbon cable to connector J9 on the OM1 card to connector J8 on the logic card in the actuator (Figures 6 and 7)
Connector J9
Connector J8
Fig. 6
Fig. 7
Connect the 8-pin connector to connector J3 on the OM1 card (figure 8)
Connect the 4-pin white connector to connector J2 on the OM1 card (figure 9).
8-pin connector
4-pin connector
Fig. 8
Fig. 9
4
® Copyrightby Tyco Valves and Controls. All rights reserved. A tyco International Ltd. Company
EPI2 Quarter-turn Electric Actuators Instruction and operating manual
Connect the 2-pin connector to connector J7 on the OM1 card (figure 10).
Connect the 3-pin connector to connector J6 on the OM1 card (figure 11)
3-pin connector 2-pin connector
Fig. 10 Install the three metal spacers (Models...