Niniguno
The DL05 micro PLC family includes eight different models. Each has eight inputs and six outputs in the base unit. The DL05 has one option module slot, which can be used to expand the I/O count, provide additional communications capability or add a real-time clock and battery back-up. The larger DL06 micro PLC family has 20 inputs and 16 outputs in the baseunit. The DL06 has four option module slots which can be used to add I/O or provide additional communications options.
DL05
8 in/6 out
Communication ports
The DL06 CPU offers PID capability, floating point number handling, and an instruction set very similar to our D2-260 CPU, including the IBox instructions available in DirectSOFT version 5. All DL06 PLCs have two built-in communicationsports that can be used for programming, operator interface, networking, etc. One of the DL06 ports is a multi-function port capable of RS-232, RS-422, or RS-485 communications.
The DL05 CPU offers PID capability, highspeed counting, and most of the same powerful instruction set as our popular D2-250-1 CPU, including the IBox instructions available in DirectSOFT version 5. All DL05 PLCs have twobuilt-in RS-232 communications ports that can be used for programming, operator interface, networking, etc.
Instruction sets
DL06
20 in/16 out
Option modules
Optional LCD display
Power options
The DL05 and DL06 families have AC and DC power options. They are also offered with a variety of I/O options. You can explore the Quick Selection Guide on the next page to choose the rightPLC for your application.
Communication ports
General Specifications
Power Input Voltage Range Maximum Power Maximum Inrush Current Storage Temperature Ambient Operating Temperature Ambient Humidity Vibration Resistance Shock Resistance Noise Immunity Atmosphere
95-240VAC
AC Powered
110/220VAC (+ 10%, -15%), 50-60Hz
DC Powered
12/24VDC 12-24VDC 20W 10A < 1ms
Units with DC inputshave selectable highspeed input features on three input points (DL05) or four input points (DL06). Units with DC outputs can use the first two outputs as a single bi-directional pulse output. An overview of the high-speed I/O features appear later in this section.
High-speed inputs and outputs
30VA (DL05) 40VA (DL06) 13A, 1ms (240VAC) -4ºF to 158ºF (-20ºC to 70ºC) 32°F to 131°F (0°C to 55°C)5% - 95% relative humidity (non-condensing) MIL STD 810C, Method 514.2 MIL STD 810C, Method 516.2 NEMA (ICS3-304) No corrosive gases
Volume 14
e2-18
Programmable Controllers
1 - 80 0 - 633 - 0405
Quick Selection Guide
110/220 (+10%, -15%) VAC Power Options
DL05 D0-05AA 8 AC inputs 6 AC outputs, 0.5A/point D0-06AA 20 AC inputs 16 AC outputs, 0.5A/point DL06 D0-06DD1 20 DCinputs Four inputs are filtered inputs, can also be configured as a single 7kHz high-speed counter, interrupt input, or pulse catch input 16 DC outputs (sinking), 1.0A/point* Two outputs can be used as a single bi-directional 10kHz pulse output
Company Information Systems Overview Programmable Controllers Field I/O Software C-more & other HMI Drives Soft Starters Motors & Gearbox Steppers/ ServosMotor Controls Proximity Sensors Photo Sensors Limit Switches Encoders Current Sensors Pressure Sensors Temperature Sensors Pushbuttons/ Lights Process
D0-05AD 8 AC inputs 6 DC outputs (sinking), 1.0A/point Two outputs can be used as a single bi-directional 7kHz pulse output D0-05AR 8 AC inputs 6 relay outputs, 2A/point
D0-06AR 20 AC inputs 16 relay outputs, 2A/point
D0-05DA 8 DC inputsThree inputs are filtered, or configure as a single 5kHz high-speed counter, interrupt input, or pulse catch input 6 AC outputs, 0.5A/point D0-05DD 8 DC inputs Four inputs are filtered, or configure as a single 5kHz high-speed counter, interrupt input, or pulse catch input 6 DC outputs (sinking), 1.0A/point Two outputs can be used as a single bi-directional 7kHz pulse output
D0-06DA 20 DC...