Hoja De Calculo
DATOS: POTENCIA=276,558.00 WATT. VOLTAGE= 220 VOLT. LONGITUD= 40 (distancia indicada por supervision) e%= 3 % FP.= 95 IN= CORRIENTE NOMINAL 764.8809 AMP. IC=CORRIENTE CORREG. 856.6666 AMP. POR CORRIENTE POTENCIA 276558 FD. 1 VOLT. 220 RAIZ 1.73 FP 0.95
CM1
R-1 276558
R-2 361.57
IN AMPERES764.8809359
FATC./CORR. AGR./TEMP 1.12
IC. 856.667
12,COND. 400 KCM.
S=202.7mm2 AMP= 335
POR CAIDA DE TENSION
R-1 2 RAIZ1.73 LONG 40 IC 857 VOLT. 220 e% 3 118562.7
R-2 660
SECC. TRANV-mm2 179.6404002
9 COND.
KCM.
S= A=
SE DESCARTA ESTE PASO , YSE SOPORTA
POR CAIDA DE TENSION REAL
R-1 2 RAIZ 1.73 DIST 40 IC 857 VOLT. 220 S/mm2 202.7 118562.7
R-2 44594
CAIDA DE TEN,REAL2.658713372
POR FASE NEUTRO
3 COND. 400 KCM. 3,COND.400KCM.
S= 202.7 mm2 A=335
DE PROYECTO
POR FASE 3, COND. NEUTRO 3,COND.TIERRAS 3,COND. 3,T-DE 75 MM. POR FASE 3, COND. NEUTRO 3,COND. TIERRAS 3,COND. 3,T-DE 100 MM.
300 KCM. 300 KCM. 1/0
ACTUALIZADO EL4-MAYO-2012
PROPUESTA
400 KCM. 400 KCM. 1/0
CONDUCT. POR FASE 3
CORRIENTE POR HILO 285.5555494
CONDUCT. POR FASE 3
SECC. TRANSV.POR HILO 59.88013339
ARTA ESTE PASO , Y SE SOPORTA EN LA CAIDA DE TENSION REAL.
CONDUCT. POR FASE 3
e% DEL SISTEMA 0.886237791