Cuestionario
TC1
TC2
CALCULO DE CALIBRE DE CONDUCTORES PRINCIPALES
CARGA TOTAL = 685.2 amp
FACTOR DE UTILIZACION
I= (0.6) (685.2) = 411.12 amp
P = 3 V I
P = 3 (220v)(411.12 amp) = 156.65 KVA
TRANSFORMADOR DE 250 KVA
I = P / 3 V = 250kv / 3 (13.2kv) = 250 kv / 22.86 kv = 10.93amp
Ip = (10.93amp) (1.25%) = 13.66
LISTON FUSIBLE = 15amp
AJUSTE PARA LAPROTECCION DEL SECUNDARIO
I = P/ 3 V
I = 250kv / 3 (.220) = 250kv / 0.38105177 = 656.07amp
3X700
AJUSTE PARA LA PROTECCION DEL TC2
I = 99.20kv/ 3 (.220) = 99.20kv / 0.381051177 =260amp
3X300
SECCION DE BASES
S = 1000kv
V = 13.2kv
CONVERSIÓN DE IMPEDANCIAS A UNA BASE COMUN
COMPAÑÍA SUMINISTRADORA
XP.U = KVA base / KVA compañía sum.
XP.U = 1000 / 10,000 =0.01 p.u
CALCULO DE POTENCIA DE MOTORES
P = V I * n * FP / 746
LAVADORAS
I = 12 V = 220 n = 0.8 FP = 0.85
PHp = (220) (12) (0.8) (0.85) / 746 = 1795.2 / 746 = 2.40 Hp
SECADORASI = 3 V = 220 n = 0.8 FP = 0.85
PHp = (220) (3) 0.8) (0.85) / 746 = 448. 8 / 746 = 0.60 Hp
CLIMAS
I = 7.5V=220 n = 0.8 FP = 0.85
PHp = (220) (7.5) (.8) (0.85) / 746 = 1122 / 746 = 1.5Hp
IMPEDANCIA DE MOTORES
XP.U = KVA base x motor / KVA motor
LAVADORAS
XP.U = 1000 / 2.40 (.25) = 104.16 p.u
SECADORAS
XP.U = 1000 / 0.60 (.25) = 416.6 p.u
CLIMAS
XP.U = 1000 /1.5 (.25) = 166.6 p.u
Z BASE BUS 1
Z base = (KVA real) 2 / KVA base (1000)
Z base = (13.2)2 / 1000 (1000) = 174.24
Z P.U = Z real / Z base = 0.0147 / 174.24 = 8.43X10-3
REACTANCIA/ m = 0.135
X = (0.135) (.030) = 4.05X10-3
BUS 2
Z base = (.220)2 (1000) / 1000 = 0.0484
Z P.U = 4.05X10-3 / 0.0484 = 0.083
REACTANCIA / m = 0.117
X = (0.117) (0.045) = 5.26X10-3Z P.U = 5.26X10-3 / 0.0484 = 0.10
CONTINUACION DE DE DIAGRAMA DE IMPEDANCIAS
ZT = 0.080
I P.U = 1/ Z P.U = 1 / 0.080 = 12.5 amp
I P.U = 12.5 amp
I base = KVA base / 3 V base = 1000 /...