Estudiante
Catalog 8910CT9301R04/10
2011
Class 8910, 8911, 8965, 9998, 9999
CONTENTS Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page Contactors, Types DP and DPAClass 8910 . . . . . . . . . . . . . . . . . . . . . . .3 Starters, Types DPS and H through MClass 8911 . . . . . . . . . . . . . . . . . .7Reversing/Hoist Contactors, Type DPRClass 8965 . . . . . . . . . . . . . . . . .8 Reversing/Hoist Contactors, Type RClass 8965. . . . . . . . . . . . . . . . . . . 11 Replacement Parts KitsClass 9998 . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 External Auxiliary ContactsClass 9999. . . . . . . . . . . . . . . . . . . . . . . . . .14
PDF created with pdfFactory trial versionwww.pdffactory.com
PDF created with pdfFactory trial version www.pdffactory.com
Definite Purpose Control
Contactors, Types DP and DPAClass 8910
Contactors, Types DP and DPAClass 8910
Definite purpose contactors are ideal for heating, air conditioning, refrigeration, data processing, and food service equipment. New, compact 1- and 2-pole contactors are available as well as full-size devices with2, 3, or 4 poles. They feature the following:
‹ Ÿ Ÿ Ÿ Ÿ
Quick connect terminals and binder head screws allow for easy wiring. Box lugs are standard on 40 A contactors and larger. An exclusive DIN track mounting option may reduce installation costs. Coils can be changed quickly, without a tool, on the Type DPA, 5090 A contactors. Auxiliary contact modules snap on either side of the Type DPAcontactors. Compact 1-Pole Contactors600 Vac Maximum
Locked Rotor Amperes 277 V 120 150 150 240 460 V 100 125 125 200 575 V 80 100 100 160 Resistive Load Amperes 25 30 40 50 [2] N.O. Poles 1 1 1 1 Type [1] DP11 DP21 DP31 DP41
Table 1:
Full Load Amperes 20 25 30 40
1 2
Specify the voltage code when ordering this product. Refer to Table 7 on page 4. 50 A resistive limited to 277 V. Voltagesabove 277 V are rated 40 A resistive.
Type DP22V09 2 pole
Table 2:
Full Load Amperes 20 25 30 40
1 2
Compact 2-Pole Contactors600 Vac Maximum [1]
Locked Rotor Amperes 277 V 120 150 150 240 460 V 100 125 125 200 575 V 80 100 100 160 Resistive Load Amperes 30 35 40 50 N.O. Poles 2 2 2 2 Type [2] DP12 DP22 DP32 DP42
Above 240 V, all lines must be switched. Specify the voltage codewhen ordering this product. Refer to Table 7 on page 4.
Table 3: Type DP42V14 2 pole
Full Load Amperes 20
2, 3, and 4-Pole Contactors600 Vac Maximum [1]
Locked Rotor Amperes 230 V 120 460 V 100 575 V 80 Resistance Load Amperes 30 Horsepower Ratings 115 V, 1Ø 230 V, 1Ø 230 V, 3Ø 460/575 V, 3Ø 1.5 3 7.5 7.5 N.O. Poles 2 3 4 2 3 4 2 3 4 2 3 4 2 3 2 3 2 3 2 3 Type [2] DPA12 DPA13 DPA14 DPA22DPA23 DPA24 DPA32 DPA33 DPA34 DPA42 DPA43 DPA44 DPA52 DPA53 DPA62 DPA63 DPA72 DPA73 DPA92 DPA93
25
150
125
100
35
2
5
10
15/20
30
180
150
120
40
2
5
10
15/20
40 50 60
240 300 360 450 540
200 250 300 375 450
160 200 240 300 360
50 62 75 94 120
3 3 5 5 7.5
7.5 10 10 15 20
10 15 25 25 30
20/25 30 30 40 50
Type DPA33V043 pole
1 2
75 90
Above 240 V, all lines must be switched. Specify the voltage code when ordering this product. Refer to Table 7 on page 4.
© 19982011 Schneider Electric All Rights Reserved
3 04/2011
PDF created with pdfFactory trial version www.pdffactory.com
Definite Purpose Control
Contactors, Types DP and DPAClass 8910
Table 4:
ݱ²¬¿½¬±®
2 N.O. and 2 N.C. 4-PoleContactors600 Vac Maximum [1]
Resistive Load Amperes 25 35 40 N.O. Poles 2 2 2 N.C. Poles [2] 2 2 2 Class 8910 Type [3] DPA14 DPA24 DPA34 Form Y392 Y392 Y392
Full Load Amperes 20 25 30
1 2 3
Þ±¬¬±³ Ì¿¾-
̱° ر±µÑ°»®¿¬·²¹ Ì¿¾
Above 240 V, all lines must be switched. The N.C. poles are on the outside. The N.C. poles open before the N.O. poles close. Specify the voltage code when...
Regístrate para leer el documento completo.