Hoy bien hecho
Project 89ME4819/E125359
Issued: 1989-10-19
Revised: 2003-12-09
REPORT
on
EMERGENCY LIGHTING AND POWER EQUIPMENT
Cooper Industries Inc.
Cooper Lighting, Div. of
Peachtree, GA
Copyright 1989 Underwriters Laboratories Inc.
Underwriters Laboratories Inc. authorizes the above-named company to reproduce this Report provided it is reproduced in its entirety.File E65048 Vol. 1 Sec. 52 Page 1 Issued: 1989-10-19
and Report Revised: 2003-12-09
DESCRIPTION
PRODUCT COVERED:
Unit Equipment - Models 6 followed by A or X; followed by C; followed by NY; followed by 1, 3, 4, 5 or 7. Model 12 followed by A or X; followed by C; followed by NY; followed by 2, 3, 4 or 5. Models 6 followed by A or X; followed by C; followed by 10, 27, 36, 54,or 100. Models 12 followed by A or X; followed by C; followed by 30, 36, 54, or 100. Model 12 followed by H or X; followed by C; followed by 200, 300, or 400. Model 12 followed by H or X followed by C; followed by NY; followed by 7, 8, or 9. Model 12 followed by B; followed by C; followed by NY; followed by 2, 3, or 4. Model 12 followed by B; followed by C; followed by 30, 36, or 54.Models 6BC10, 6BC27 and 6BCNY1. Models R, prefixed by 6 or 12; followed by OB; followed by 10 or 24.
GENERAL CHARACTERISTICS AND USE:
(Unit Equipment)
The devices covered by this report are emergency lighting units intended to provide a source of illumination in the event of an ac power supply failure. These units are for permanent (conduit knockouts provided) installation or cord connection(cord provided). Each unit is provided with a battery and battery charging circuit. Provision for remote lampheads.
File E65048 Vol. 1 Sec. 52 Page 2 Issued: 1989-10-19
and Report Revised: 2003-12-09
RATINGS
Batteries
NY
Input
Output
Discharge
Atlite
Rating
Model
Model
V
A
V
W
Time (h)Part No.
Mfr's
Type
(V, AH)
Amount
PWA
XFMR
6AC10
-
120/277
42
6
10
1-1/2
24-1001
EP
CFM6V4.6
6, 4.6
1
55-1002
12-1101
24-1002
PANA
LCR6V4P
6, 4
1
55-1001
CSB
GP4-6
6, 4
1
6AC27
6ACNY1
120/277
42
6
27
1-1/2
24-1004
EP
CFM6V9.5
6, 9.5
1
55-1002
12-1101
24-1003
EP
CFM6V10
6, 10
1
55-1001
PANA
LCR6V10R
6, 10
1
PS
PS6100F6, 10
1
CSB
CP10-6
6, 10
1
6AC36
6ACNY3
120/277
42
6
36
1-1/2
24-1004
EP
CFM6V9.5
6, 9.5
2P
55-1002
12-1101
24-1003
PANA
LCR6V10R
6, 10
2P
6AC54
6ACNY4
120/277
42
6
54
1-1/2
24-1004
EP
CFM6V9.5
6, 10
2P
55-1002
12-1104
24-1003
PANA
LCR6V10R
6, 10
2P
55-1003
12-1104
12AC100
6ACNY5
120/277
10
6
100
1-1/2
24-1006
EP
CFM6V33
6, 33
1PWR
PRC636
6, 36
1
PM
PM6360
6, 36
1
55-7001
12-1103
6AC200
6ACNY7
120/277
14
6
200
1-1/2
24-1006
EP
CFM6V33
6, 33
2P
55-1003
12-1104
PM
PM6360
6, 36
1
55-7001
12-1103
12AC30
12ACNY2
120/277
42
12
27
1-1/2
24-1007
EP
CFM6V6
6, 6
2S
55-1002
12-1201
24-1003
PANA
LCR6V10R
6,10
2S
55-1002
12-1201
BB
BP10-6
6,10
2S
55-6001M
12-1103RBB -
BB Battery
PS -
Power Sonic
CSB -
China Storage Battery
PWA -
Printed Wiring Assembly
EP -
Eagle Picher
PWR -
Power Battery
P -
Parallel
S -
Series
PANA -
Panasonic
SP -
Series Parallel
PM -
Power Mate
XFMR -
Transformer
File E65048 Vol. 1 Sec. 52 Page 3 Issued: 1989-10-19
and Report Revised: 2003-12-09
RATINGSBatteries
NY
Input
Output
Discharge
Atlite
Rating
Model
Model
V
A
V
W
Time (h)
Part No.
Mfr's
Type
(V, AH)
Amount
PWA
XFMR
12AC36
12ACNY3
120/277
12
36
1-1/2
24-1004
EP
CFM6V9.5
6, 9.5
2S
55-1002
12-1201
24-1011
PANA
LCR6V6.5
6, 6.5
2S
55-6004M
12-1201R
12AC54...
Regístrate para leer el documento completo.